iSN-104
No items found.

iSN-104

ICP DAS iSN-104 is a 4-channel intelligent liquid leak detection module that simultaneously monitors four independent detection zones — each supporting cable or probe sensors up to 500 meters — with a built-in audible buzzer, five LED indicators, adjustable sensitivity per channel, cable-break detection, and RS-485 Modbus RTU/DCON communication. Designed for critical environments such as data centers, warehouses, libraries, and industrial facilities, the iSN-104 delivers multi-zone leak monitoring in a compact DIN-rail form factor.

  • 4 independent liquid leak detection channels — simultaneous multi-zone monitoring
  • Detection cable up to 500 meters per channel (probe or cable sensor)
  • Cable-break detection supported (CA-LLD-DC100X waterproof plug cable)
  • Per-channel adjustable sensitivity: 26 kΩ–580 kΩ via rotary switch
  • 5 LED indicators: 1 power + 4 independent alarm LEDs (one per channel)
  • Built-in audible buzzer with mute button | Sound on/off via DIP switch SW5
  • RS-485 Modbus RTU & DCON protocol — hardware DIP switch configuration
  • Embedded dual watchdog | ESD ±8 kV Air | EFT ±4 kV
  • DIN-rail mounting | Compact: 72 × 95 × 57 mm
  • Power: +10–30 VDC | 1.6 W max. | -25°C to +75°C | RoHS compliant

ICP DAS iSN-104 is a 4-channel intelligent liquid leak detection module that extends the single-channel iSN-101 capability to four independent detection zones in a single DIN-rail unit. Each channel independently monitors for liquid presence using either a line detection cable or a point detection probe, with each cable run extendable up to 500 meters — enabling coverage of large, multi-zone facilities from a single module.

The iSN-104 supports two detection configurations per channel. Cable mode deploys a liquid leak detection cable (CA-LLD-DC100) along pipe runs, floor channels, or under raised floors for continuous linear monitoring — ideal for data center subfloors, mechanical rooms, and refrigeration corridors. Probe mode positions a leakage probe (CA-LLD-DP100) at specific point locations such as drain pans, sump pits, and equipment bases. The waterproof plug-type cable (CA-LLD-DC100X) additionally supports cable-break detection, providing fault monitoring of the detection cable itself for enhanced reliability.

Sensitivity for each channel is independently adjustable via front-panel rotary switches across a range of 26 kΩ to 580 kΩ, enabling precise threshold tuning per zone to account for differences in liquid conductivity, ambient humidity, and cable length. Five LED indicators — one power and four independent alarm LEDs (one per channel) — provide immediate visual identification of which zone has triggered an alarm without needing to consult a software interface.

The built-in audible buzzer activates on any channel alarm and can be silenced via a dedicated mute push button, with a separate DIP switch (SW5) option to disable the buzzer entirely for noise-sensitive environments. RS-485 Modbus RTU and DCON protocol support, with hardware DIP switch address and mode configuration, enables seamless integration into multi-module networks and ICP DAS WISE IoT Edge Controllers or TPD/VPD touch HMIs for centralized remote monitoring and alarm management.

Compared to the iSN-101, the iSN-104 adds 3 additional detection channels, a 5th alarm LED, a sound on/off DIP switch (SW5), and upgrades to a DIN-rail form factor — making it the preferred choice for multi-zone installations requiring independent per-zone alarm visibility from a single unit.

Technical Specifications — ICP DAS iSN-104
General
ModeliSN-104 (4-Channel Liquid Leak Detection Module)
Dimensions (W × L × H)72 × 95 × 57 mm
InstallationDIN-rail mounting
ComplianceRoHS compliant
Liquid Leak Detection
Channels4 independent channels
Liquid TypeWater (conductivity ≥2 µS/cm)
Sensor TypeProbe (point detection) or Cable (line detection) per channel
Max. Cable Length500 meters per channel (including extended cable)
Sensitivity Range26 kΩ to 580 kΩ — adjustable per channel via rotary switch
Cable-Break DetectionSupported (CA-LLD-DC100X waterproof plug cable only)
Alarm & Indicators
LED Indicators1 × Power LED | 4 × Alarm LED (1 per channel — independent)
BuzzerBuilt-in audible alarm — mutable via push button
Sound On/OffDIP switch SW5: ON = Sound On | OFF = Sound Off
Alarm TriggerLiquid leak detection & cable-break detection (per channel)
Communication
Interface1 × RS-485
ProtocolsModbus RTU | DCON (selectable via DIP switch SW1)
Baud Rate1,200 to 115,200 bps (software configurable)
Data Format(N,8,1) | (O,8,1) | (E,8,1) | (N,8,2)
DIP Switch Configuration
SW1ON: DCON Protocol | OFF: Modbus RTU Protocol
SW2ON: Software configuration | OFF: Hardware configuration
SW3ON: High node address | OFF: Low node address
SW4ON: INIT mode | OFF: Normal mode
SW5ON: Sound On | OFF: Sound Off
EMS Protection
ESD Protection±8 kV Air for random point (IEC 61000-4-2)
EFT Protection±4 kV for power (IEC 61000-4-4)
WatchdogEmbedded dual watchdog
Power
Input Voltage+10 to +30 VDC
Power Consumption1.6 W max.
Reverse Polarity ProtectionYes
Environmental & General
Operating Temperature-25°C to +75°C
Storage Temperature-30°C to +80°C
Humidity10–90% RH, non-condensing
Comparison: iSN-104 vs iSN-101
iSN-104 (this model)4 channels | DIN-rail | 5 LEDs | Sound on/off DIP switch | 72×95×57 mm
iSN-1011 channel | Wall mount | 2 LEDs | No sound DIP switch | 83×70×29 mm
Key Accessories (Sold Separately)
Leak Detection CableCA-LLD-DC100-L100/L300/L500 — 10 m / 30 m / 50 m
Extended Cable (Waterproof)CA-LLD-DC100X-L010/030/100/300/500 — 1 m to 50 m
Leakage ProbeCA-LLD-DP100
Terminal ResistorCA-LLD-DC100X-TR — 2 MΩ
Hold-Down ClipsASO-0051 (180°) | ASO-0052 (90°) — 50 pcs each
RS-485 ConvertertM-7561 (USB) | tM-7520U (RS-232) | I-7514U (4-ch RS-485 Hub)

* Specifications are based on the iSN-104 datasheet (ICP DAS, Rev. 2023.06). Specifications subject to change without notice. Please refer to the official ICP DAS datasheet for the most up-to-date information.

#liquid leak detection #icpdas #4 channel leak sensor #water leak detector #modbus rtu #rs485 sensor #din rail #iiot